Skip image slider
TPB1-63 AC miniature circuit breaker front view
TPB1-63 AC miniature circuit breaker front view

TPB1-63 AC Miniature Circuit Breaker(MCB) for Load Safety

Breaking capacity(TPB1-63:3kA;TPB1-63H:4.5kA;TPB3-63:6kA;TPB3-63H:10kA)

TPB1-63 Miniature Circuit Breaker (MCB) is designed for AC 50/60Hz electrical circuits with a rated voltage up to 400V and a rated current up to 63A. It provides reliable overload and short-circuit protection, and can also be used for infrequent circuit switching under normal Operating conditions.
It is widely suitable for residential distribution boards, commercial premises, industrial control panels, and high-rise building electrical systems.
Standard: IEC 60898-1
Products Categories
Get A Free Quote
Contact Form

Type designation

TPB1-63(H) 1P C 63A

TP B1 63 H 1P C 63A
Company code Series code Frame Breaking capacity Poles Curve Current(In)
TP B1 63 No: 3kA
H: 4.5kA
1P
2P
3P
4P
B
C
D
1A~63A

Technical data

Type Parameter Unit Specification
– Standard – IEC/EN 60898-1
Electrical features Rated current In A 1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63
Poles P 1,2,3,4
Rated voltage Ue V 230/400
Insulation voltage Ui V 500
Rated frequency Hz 50/60
Rated breaking capacity A 3000, 4500
Rated impulse withstand voltage(1.2/50)Uimp V 4000
Dielectric test voltage at ind. Freq. for 1min kV 2
Pollution degree – 2
Thermo-magnetic release characteristic – B,C,D
Mechanical features Electrical life t 6000
Mechanical life t 20000
Protection degree – IP20
Reference temperature for setting of thermal element °C 30
Ambient temperature (with daily averages≤35°C) °C -5~+40
Storage temperature °C -25~+70
Installation Terminal connection type – Cable/Pin-type busbar
Terminal size top/ bottom for cable mm² 25
AWG 18-3
Terminal size top/ bottom for busbar mm² 25
AWG 18-3
Tightening torque N*m 2
In-lbs 18
Mounting – On DIN rail EN 60715(35mm)by means of fast clip device
Connection – From top or bottom

Selection

  • Curve Type
Curve Type Test current Tripping time Expected result
B,C,D 1.13In t≤1h(In≤63A) Not tripping
1.13In t≤2h(In>63A)
B,C,D 1.45In t≤1h(In≤63A) Tripping
1.45In t<2h(In>63A)
B,C,D 2.25In 1s<t<60s(In≤32A) Tripping
2.25In 1s<t<120s(In>32A)
Curve Type Test current Tripping time Expected result
B 3In t≤0.1s Not tripping
C 5In t≤0.1s
D 10In t≤0.1s
B 5In t<0.1s Tripping
C 10In t<0.1s
D 20In t<0.1s
  • Curve

Curve-of-TPB1-63-MCB

  • Temperature drop correction table

Miniature Circuit Breaker current performance is temperature-dependent. Ambient temperature means the temperature inside the enclosure(distribution box/switch cabinet) at the installation location. Refer to the rows in the table for the corresponding reference temperatures.Product standard: GB/T 10963.1, IEC 60898-1(household standard)

Rated current temperature
-5 °C 0 °C 5 °C 10 °C 15°C 20°C 25°C 30°C 35°C 40°C 45°C
1A 1.16 1.14 1.11 1.09 1.07 1.05 1.02 1.00 0.98 0.95 0.92
2A 2.30 2.26 2.22 2.18 2.13 2.08 2.04 2.00 1.96 1.92 1.88
4A 4.72 4.63 4.53 4.43 4.32 4.22 4.11 4.00 3.89 3.77 3.65
6A 6.97 6.84 6.71 6.57 6.43 6.29 6.15 6.00 5.85 5.69 5.53
10A 12.25 11.95 11.65 11.34 11.02 10.69 10.35 10.00 9.64 9.26 8.86
16A 18.72 18.35 17.98 17.60 17.22 16.82 16.42 16.00 15.57 15.13 14.68
20A 23.24 22.80 22.36 21.91 21.45 20.98 20.49 20.00 19.49 18.97 18.44
25A 29.12 28.57 28.01 27.43 26.85 26.24 25.63 25.00 24.35 23.69 23.01
32A 37.18 36.49 35.78 35.05 34.32 33.56 32.79 32.00 31.19 30.36 29.50
40A 46.66 45.77 44.86 43.93 42.98 42.01 41.02 40.00 38.96 37.88 36.78
50A 58.57 57.43 56.26 55.06 53.84 52.59 51.31 50.00 48.65 47.27 45.84
63A 74.73 73.17 71.57 69.94 68.27 66.56 64.81 63.00 61.14 59.22 57.24

Overall and mounting dimensions(mm)

Dimension-Drawing-of-TPB1-63-MCB-AC-Miniature-Circuit-Breaker

Related Products

Related News