TPW3 Series ACB Air Circuit Breaker for Low Voltage Distribution
Reliable low voltage air circuit breaker for intelligent circuit protection and power distribution in industrial, commercial, and building electrical systems.
The TPW3 Series ACB air circuit breaker is engineered for low-voltage power distribution systems requiring reliable protection and stable operation. Suitable for AC 50/60Hz systems with rated voltages of 400V and 690V and current ratings from 200A to 6300A, it provides effective protection against overload, short-circuit, undervoltage, and earth fault conditions. With intelligent and selective protection functions, it helps improve electrical system safety, maintain power continuity, and reduce unnecessary downtime. Widely used in industrial plants, power stations, mines, and smart building projects, the TPW3 air circuit breaker meets IEC/EN 60947-2 standards.
Frame-type circuit breaker Type designation
TPW3- □/□ + Installation + Control unit + Common use accessory + Optional accessory
| TP | W3 | □ | □ | Installation | Control unit | Common use accessory | Optional accessory |
| Company code | Series code | Rated current in scope of frame size | Poles | Installation | Intelligent controller | Common use accessory | Optional accessory |
| TP | W3 | 1600 Type In: 200A,400A,630A,800A,1000A,1250A,1600A
2000 Type In:630A,800A,1000A,1250A,1600A,2000A 2500 type In:630A,800A,1000A,1250A,1600A,2000A,2500A 3200 Type In: 2000A,2500A,3200A 4000 Type In: 2500A,3200A,4000A 6300 Type In:4000A,5000A,6300A |
3-3 pole(default) 4-4 pole |
Fixed type-horizontal Drawout type-horizontal, vertical(Default horizontal wiring) |
M type2M type: digital display, over-current protection (overload,short delay, instantaneous),4P or 3P+N have earthing protection.
3M type: LCD display, over-current protection(overload,short delay,instantaneous), 4P or 3P+N have earthing protection. H type2H type: communication function, digital display, over-cur-rent protection(overload,short delay, instantaneous), 4P or 3P+N haveearthing protection. 3H type:communication function, LCD display, over-cur-rent protection (overload,short delay,instantaneous),4P or 3P+N have earthing protection. |
Shunt release-AC220V/230V,AC380V/400V,DC220V,DC110V
Undervoltage release-AC220V/230V,AC380V/400V, it is classified to instanta-neous type and time-delay type. Closing electromagnet-AC220V/230V,AC380V/400V,DC220V,DC110V Motor-driven energy-storage mecha-nism-AC220V/230V,AC380V/400V,DC220V,DC110V Auxiliary contact-4a4b,2a6b,3a3b Note: a-normal open, b-normal close |
Mechanical interlock;
One circuit breaker(1lock+1key) Two circuit breakers(steel cablenterlock, connecting rod inter-ock,2lock+ 1key) Three circuit breakers(3lock+2keys,connecting rodnterlock) Automatic power transfer systemCurrent transformer connectedwith neutral load |
TPW3 ACB Air Circuit Breaker Technical Data
| Item | Description |
| Number of Poles | 3,4 |
| Rated voltage Ue(V) | 400/415,660/690 |
| Rated insulation voltage Ui(V) | 1000 |
| Rated impulse withstand voltage Uimp(kV) | 12 |
| Rated frequency(Hz) | 50/60 |
| Have function of switch disconnector | ![]() |
- Frame size rated current
| Rated current In(A) | 1600 | 2000 | 2500 | 3200 | 4000 | 6300 |
| 200 | ● | |||||
| 400 | ● | |||||
| 630 | ● | ● | ● | |||
| 800 | ● | ● | ● | |||
| 1000 | ● | ● | ● | |||
| 1250 | ● | ● | ● | |||
| 1600 | ● | ● | ● | |||
| 2000 | ● | ● | ● | |||
| 2500 | ● | ● | ● | |||
| 3200 | ● | ● | ||||
| 4000 | ● | ● | ||||
| 5000 | ● | |||||
| 6300 | ● |
- Operating conditions
| Item | Description |
| Ambient temperature | -5℃~+40℃;the average value within 24h shall not exceed +35℃; L type and M type controller can be used under -40℃~+70℃ |
| Altitude | ≤2000m |
| Pollution grade | 3 |
| Safety category | Main circuit and undervoltage tripping coil is IV,other auxiliary and control circuit is III |
| Installation position | Vertically installed,inclination between the mounting plane and the vertical plane should not exceed ±5° |
- Breaking capacity
| Rated current In(A) | 1600 | 2000 | 2500 | 3200 | 4000 | 6300 | |
| Rated ultimate short circuibreaking capacity Icu(kA) | 400/415V | 65 | 80 | 100 | 100 | 120 | 135 |
| 660/690V | 50 | 65 | 70 | 85 | 85 | 100 | |
| Rated service short circuit breaking capacity Ics(kA) | 400/415V | 55 | 65 | 80 | 80 | 100 | 135 |
| 660/690V | 42 | 65 | 70 | 70 | 85 | 100 | |
| Rated short time withstand current Icw.1s(kA) | 400/415V | 50 | 65 | 80 | 80 | 100 | 135 |
| 660/690V | 42 | 65 | 70 | 70 | 85 | 100 | |
| Rated short circuit making and breaking capacity Icm(kA) | 400/415V | 110 | 176 | 220 | 220 | 264 | 297 |
| 660/690V | 77 | 143 | 154 | 154 | 187 | 220 | |
| Electric life | 8000 | 8000 | 8000 | 8000 | 600 | 1500 | |
| Mechanical life (Maintenance) | 30000 | 30000 | 30000 | 20000 | 20000 | 5000 | |
| Mechanical life (Non-maintenance) | 20000 | 15000 | 15000 | 12500 | 10000 | 2500 | |
| Dimension(mm) W×H×L | |||||||
| Drawout type | 3P | 254×297×354 | 375×389×432 | 375×389×432 | 435×389×432 | 435×389×432 | 813×389×432 |
| 4P | 324×297×354 | 470×389×432 | 470×389×432 | 550×389×432 | 550×389×432 | 928×389×432 | |
| Fixed type | 3P | 269×195×324 | 362×293×401 | 362×293×401 | 426×293×401 | 426×293×401 | 807×293×401 |
| 4P | 339×195×324 | 457×293×401 | 457×293×401 | 537×293×401 | 537×293×401 | 922×293×401 | |
Note:6300A only has 3P drawout type.
- Protection features of intelligent controller
| Digital display intelligent controller | ![]() |
| M type: digital display without communication H type: digital display with communication | |
| 01. bottom fixing position | |
| 02. rated current | |
| 03. digital display window | |
| 04. “set” switch to setting menu | |
| 05. base plate | |
| 06. indicator |
| LCD display intelligent controller | ![]() |
| 3M type: LCD display without communication 3H type: LCD display with communication | |
| 01. bottom fixing position | |
| 02. rated current | |
| 03. digital display window | |
| 04. “set” switch to setting menu | |
| 05. base plate | |
| 06. indicator |
| M/H (standard type) intelligent controller | ![]() |
|
| 01. Current of phase A | 13. +/up | |
| 02. Current of phase B | 14. Enter | |
| 03. Current of phase C | 15. -/down | |
| 04. Current of phase N | 16. Function keys | |
| 05. Load monitoring 2 | 17. Return | |
| 06. Load monitoring 1 | 18. Set indicator | |
| 07. Unbalanced current protection | 19. Check indicator | |
| 08. Earth fault protection | 20. Save indicator | |
| 09. Self-diagnosis by the intelligent controller | 21. Test indicator | |
| 10. Short circuit instantaneous protection | 22. Alarm indicator | |
| 11. Short circuit short-time delay protection | 23. Fault indicator | |
| 12. Overload long-time delay protection | ||
| 3M/3H(LCD) intelligent controller | ![]() |
|
| 01. -/down | 09. Overload long-time delay protection | |
| 02. +/up | 10. Run indicator | |
| 03. Set | 11. Communication indicator | |
| 04. Check | 12. Short circuit short-time delay protection | |
| 05. Return | 13. Earth fault protection | |
| 06. Enter | 14. Alarm indicator | |
| 07. Test | 15. Over-voltage protection | |
| 08. Reset | 16. Short circuit instantaneous protection | |
Ordering information
| Quantity Set | |||||
| Model | Available type and rated current | Rated voltage | □ AC400V □ AC690V | ||
| TPW3-1600 | □ 200 □ 400 □ 600 □ 800 □ 1000 □ 1250 □ 1600 | Quantity Set | □ Fixed □ Draw-out □Three poles □Four poles | ||
| TPW3-2000 | □ 630 □ 800 □ 1000 □ 1250 □ 1600 □ 2000 | Quantity Set | □ Fixed □ Draw-out □Three poles □Four poles | ||
| TPW3-2500 | □ 630 □ 800 □ 1000 □ 1250 □ 1600 □ 2000 □ 2500 | Quantity Set | □ Fixed □ Draw-out □Three poles □Four poles | ||
| TPW3-3200 | □ 2500 □ 2900 □ 3200 | Quantity Set | □ Fixed □ Draw-out □Three poles □Four poles | ||
| TPW3-4000 | □ 3200 □ 3600 □ 4000 | Quantity Set | □ Fixed □ Draw-out □Three poles □Four poles | ||
| TPW3-6300 | □ 4000 □ 5000 □ 6300 | Quantity Set | □ Fixed □ Draw-out □Three poles □Four poles | ||
| Intelligent controller | Basic function | □ Overload long time delay protection □ Short-circuit short delay □ Short-circuit instantaneous | |||
| Other function | □ Earthing protection □ Load monitoring □ Ampere meter □ MCR function □ Thermo-simulating □ voltage meter □ Self-diagnosis □ Testing □ Fault records □ Communication |
||||
| Controller power | □ AC 220V □ AC 380V □ DC 220V □ DC 110V | ||||
| Standard configuration | □ Shunt release | □ Under-voltage instantaneous type | |||
| □ Under-voltage time-delay type | □ 1s □ 3s □ 5s □ 10s | ||||
| □ Closing electromagnet | □ AC 220V □ AC 380V □ DC 220V □ DC 110V | ||||
| □ Motor-driven energy-storage mechanism | |||||
| □ Auxiliary contact | □ 4 groups of changeover contacts | ||||
| Optional configuration | □ Under-voltage release | □ AC 220V □ AC 380V | |||
| □ Auxiliary contact | □ 2NO adn 6NC contacts □ 4NO and 4NC contacts □ 6NC and 4NO contacts □ 3NO and 3NC contacts (TPW3-1600 noly have 4 groups of changeover contacts) |
||||
| □ Locking device □ Horizontal interlock □ Vertical interlock □ Door interlock □ Others | |||||
Note:
1. The frame size current, rated current and auxiliary control voltage must be specified when ordering.
2. Please mark “√” or fill in figure in the relative “□”, if no mark, we will provide as usual.
3. The operational function of the intelligent controller and special requirement require additional cost