TPM1-63-125-250-320-400-630-800-1250-1600L/M Molded Case Circuit Breaker for AC Systems

Professional AC MCCB solutions for commercial and industrial electrical systems/Standard: IEC 60947-2

This molded case circuit breaker is designed for higher-current AC distribution systems in buildings, industrial facilities, and infrastructure projects. It provides overload and short circuit protection for feeders, large loads, and main incoming circuits where stronger protection capacity is needed. With wider current options, durable breaker structure, and support for low-voltage distribution applications, it helps improve protection reliability and power control.

Products Categories
Get A Free Quote
Contact Form

General

TPM1 series moulded case circuit breaker (MCCB) is developed with advanced design concepts and proven manufacturing processes. According to the rated ultimate short-circuit breaking capacity (Icu), it is available in L type (standard) and M type (high breaking) versions. Featuring a compact structure, high breaking performance, short arc distance and good vibration resistance, TPM1 is suitable for both onshore and marine power distribution applications.

TPM1 is used in AC 50Hz distribution networks with rated insulation voltage up to 800V (frame 63: up to 500V), rated operational voltage up to 690V (frame 63: up to 400V), and rated current up to 1600A. It is designed for power distribution and for protecting lines and electrical equipment against overload, short circuit, and undervoltage. For motor circuits, it supports infrequent starting and provides protection against overload, short circuit, and loss/undervoltage.

For the 63–630A three-pole models, a transparent front cover option is available, allowing easier visual inspection of operating status. The breaker can be installed vertically or horizontally.

Standard: IEC 60947-2.

Type designation

TP M1 □ □ □ □ □□□ □ □
Company code Series code Frame Inm Code of breaking capacity Operation Poles Tripping mode and inner accessory Application Option for 4P MCCB
TP M1 63,125,160,250,400,630,800,1250,1600 Code of breaking capacity: L-standard type; M-higher type; Blank for direct operation with handle, Z for operation with rotary handle, P for motor-driven operation. 2:2P 3:3P 4:4P Release method and accessories code(Table 1) 1.for power distribution 2.for motor protection There are 2 types of N-pole for 4P breaker: A:Without current release components, N-Pole is always at making
status(not breakers); B:Without current release components, N-Pole is made with the other three poles.

TPM1 AC MCCB Technical data

Type TPM1-63 TPM1-125 TPM1-160 TPM1-250 TPM1-400 TPM1-630 TPM1-800 TPM1-1250 TPM1-1600
Poles P 3 3,4 2,3 3,4 3 2,3,4 3,4 3,4 3,4 3 3
Rated current In A 10,16,20,25,32,40,50,63 10,16,20,25,32,40,

50,63,80,100,125

100,125,140,160 100,125,140 160,

180,200 225,250

200,225,250,275,

300,315,320,350,400

400,500,630 630,700,800 800,1000,1250 1600
Rated insulation voltage Ui V 500 800
Rated impulse withstand voltage Uimp V 600 8000
Rated operation voltage Ue V AC230/400/690
Breaking capacity class L M L M L L M L M L M L M L M L M
Limit short-circuit breaking capacity Icu kA 230V 35 50 35 50 35 35 50 50 75 50 75 100 100 100 100 100 100
400V 25 35 25/35 50 35 35 50 35/50 65 35/50 65 75 75 85 85 85 85
690V 5 8 8 10 8 8 10 10 20 10 20 20 30 20 30 20 30
Working short-circuit breaking capacity Ics kA 230V 18 50 22 50 22 22 50 50 50 50 50 75 75 75 75 75 75
400V 18 22 18/22 25 22 18/22 25 18/35 32.5 18/35 42.5 50 50 50 50 50 50
690V 2 4 4 5 4 4 5 5 10 5 10 10 15 10 15 10 10
Arcing distance mm 50 100
Operating life(cycle) Electrical life 3000 3000 3000 3000 2000 2000 2000 800 500
mechanical life 20000 20000 20000 20000 10000 10000 10000 5000 2500

Curve of TPM1 Molded Case Circuit Breaker

Cure-of-TPM1-MCCB

Operating conditions

  • Temperature: -5°C~+40°C; the average value within 24h shall not exceed +35°C. For the circuit breaker with

thermo-magnetic release, +40°Cis set to be the standard temperature for ratings. For temperature not between

-5°C~+40°C, please contact us for temperature compensation

correction;

  • Altitude: not exceed 2000m (Please contact with us for reduction coefficient if altitude at the mounted site exceed

2000m)

  • Pollution grade: Grade 3;
  • Air conditions:At mounting site, relative humidity not exceed 50% at the max temperature of +40°C, higher

relative humidity is allowable under lower temperature. For example, RH could be 90% at +20°C. Special measures

should be taken when dew occurs.

Dimensions(mm)

Type Overall size (mm) Installation size (mm)
W L H W1 W2 L1 H1 H2 A B Φd
TPM1-63L 78 135 74 50 – 156 92 28 25 117 3.5
TPM1-63M 78 135 82 50 103 156 100 28 25 117 3.5
TPM1-125L 92 150 68 60 – 200 88 24 30 129 4.5
TPM1-125M 92 150 86 60 122 200 105 24 30 129 4.5
TPM1-160L 93 151 76 60 – 200 96 24 30 129 4.5
TPM1-250L 107 165 86 70 – 215 110 24 35 126 5
TPM1-250M 107 165 103 70 142 215 127 24 35 126 5
TPM1-400L 150 257 107 96 198 357 162 38 44 194 7
TPM1-400M 150 257 107 96 198 357 162 38 44 194 7
TPM1-630L 182 271 112 116 240 370 165 42 58 200 7
TPM1-630M 182 271 112 116 240 370 165 42 58 200 7
TPM1-800L/M 210 280 116 140 280 385 168 42 70 243 7
TPM1-1250L/M 210 406 158 140 – 610 193 60 70 375 11
TPM1-1600L/M

Dimension-Drawing-of-TPM1-MCCB

Download TPM1 AC MCCB Datasheet

Related Products

Related News

Scroll to Top

Get Your Quote Within 24 Hours

Contact Form
Our engineering team will reply with a tailored quotation and confirmed lead time within 24 hours.
Get A Free Quote

Get Your Quote Within 24 Hours

Contact Form (#6)
Our engineering team will reply with a tailored quotation and confirmed lead time within 24 hours.
Get A Free Quote